The user must ensure that portable fire extinguishers are checked and maintained.
The competent person must carry out maintenance every year, with a tolerance of plus or minus two months.
Any portable extinguisher (body or equipment) must be deemed unusable by the competent person when he considers:
- That its condition is unsafe
- That it would be dangerous to use
- That its condition may prevent it from operating satisfactorily, e.g. loss of contents or pressure in excess of tolerances;
- That the information necessary for its use has become illegible
The competent person must draw up a report, no later than at the end of the site visit, to notify the user of any portable extinguisher requiring corrective action.
The competent person must check that the portable extinguisher complies with current regulations and that it is not of a type defined in article 6 of standard NF S61-919.
The competent person must affix the marking "VERIFIED" to any portable extinguisher which, after verification and, if necessary, repair and replacement of illegible labels, is fit for continued operation.
In addition, the information must be recorded in a register.
Make sure your extinguishers are regularly inspected and maintained in accordance with international and national standards. For total peace of mind, call on Scutum Incendie technicians to carry out these important extinguisher checks.