Fire Safety in Data Centres: Protecting Your Critical Data

Written by Guillaume Brizot

A data centre is not just another computer room. It is the digital heart of a business: this is where servers, storage arrays, backup systems and the entire network infrastructure that keeps operations running day after day are housed. Within just a few dozen square metres, an enormous amount of value is concentrated, both tangible and intangible.

Why Is Fire Safety Critical in Data Centres?

Data centres house essential IT infrastructure, including servers, electrical systems and backup power supplies. Despite carefully controlled environments, these facilities can present significant fire risks due to electrical equipment, battery systems and the heat generated during normal operations.

A fire can have serious consequences, potentially damaging critical infrastructure, disrupting services and resulting in data loss, financial costs and reputational harm.

Effective fire protection therefore requires a specialist approach that considers the unique risks associated with data centre operations. Early detection, appropriate fire suppression and robust emergency procedures are essential considerations when protecting critical equipment and maintaining business continuity.

Data center.png

Common Causes of Fire in Data Centres

Understanding the potential causes of fire is essential to developing an effective fire protection strategy.

Data centres present several specific fire hazards associated with electrical infrastructure, battery systems and equipment operation. Identifying these risks helps organisations implement appropriate prevention, detection and suppression measures.

Router

Electrical Risks

Electrical faults are a significant potential source of fire in data centres. These may include short circuits, overloaded Power Distribution Units (PDUs) and faults within Uninterruptible Power Supply (UPS) systems.

Battery systems also require particular consideration. Lithium-ion batteries, used in some backup power installations, can experience thermal runaway, a process in which rising temperatures trigger a self-sustaining reaction that can lead to fire and the release of hazardous gases.

fire-icon

Equipment Overheating

Equipment overheating is another potential risk. Failures in heating, ventilation and air conditioning (HVAC) systems, or poor airflow management between hot and cold aisles, can cause temperatures to rise beyond recommended operating limits.

Prolonged overheating can damage equipment and increase the likelihood of electrical faults, potentially contributing to fire risk.

Icône câble

Cabling & Electrical Infrastructure

Damaged or ageing cables, overloaded circuits and densely packed cable installations can present fire risks within data centres, particularly in areas beneath raised floors or within cable trays.

Inadequate cable management or ventilation can contribute to overheating, potentially damaging insulation and increasing the risk of electrical faults or fire.

Users

Human Factors

Human error can also contribute to fire risks, even in highly automated data centres. Incorrect maintenance procedures, accidental damage to equipment and hot work activities, such as welding or grinding, can introduce ignition sources.

Appropriate safety procedures, including risk assessments and hot work permits where required, are essential to managing these risks.

The regulatory and standards framework: what does UK law say?

Fire safety in a data centre falls within a specific regulatory and standards framework. Compliance is not simply a legal matter: it can also be a condition of insurance cover and a demonstration of professionalism towards customers and partners.

UK fire safety regulations and standards

In the UK, fire safety in data centres is governed by a combination of legislation, building regulations and technical standards. In England and Wales, the Regulatory Reform (Fire Safety) Order 2005 (RRO) provides the main legal framework for fire safety in non-domestic premises. It places responsibility on the person with overall responsibility for the premises to carry out and regularly review a suitable fire risk assessment and implement appropriate fire safety measures.

The Building Regulations and associated guidance, including Approved Document B, also provide requirements and guidance relating to fire safety, compartmentation, fire resistance and means of escape.

For fire detection and alarm systems, BS 5839-1 is a key reference standard. It provides recommendations for the planning, design, installation, commissioning and maintenance of fire detection and fire alarm systems in non-domestic premises.

Pictogramme utilisateur

Guillaume, Commercial Director at Scutum Fire

“Certification to a recognised standard has become a real argument in our discussions with our clients' insurers. A certified site can often negotiate better insurance terms, and the file is processed much more quickly than for a non-certified site. This is something we systematically highlight from the very beginning of a data centre project, because it has a direct impact on the client's overall budget.”

International standards (NFPA 75 & 76, ISO 27001)

At international level, NFPA 75 covers the protection of information technology equipment and its premises: it defines construction, compartmentation and fire protection requirements applicable to computer rooms. NFPA 76, which is more specific, applies to telecommunications facilities. These two US standards are now considered references for good practice well beyond the United States.

ISO 27001, meanwhile, is not strictly a fire safety standard: it is a standard for information security management. However, as part of the risk assessment it requires, serious consideration must be given to physical risks affecting data, of which fire is naturally one. An organisation certified to ISO 27001 must therefore be able to demonstrate that its data centre is protected in proportion to the risks identified.

The protection arsenal: fire detection solutions

When it comes to fire safety, one principle takes precedence over all others: detect as early as possible to act as quickly as possible. In a data centre, the aim is not to detect the flame, but to identify the warning signs of a fire long before it appears.

Aspirating smoke detection (HSSD / VESDA)

Aspirating smoke detection (HSSD) systems, of which VESDA is the best-known technology, operate according to a different principle from conventional detectors: a network of pipes continuously draws small quantities of air from the room and analyses them for particles that are invisible to the naked eye.

Their sensitivity can reach up to 1,000 times that of a standard smoke detector. In practical terms, this means detection at the pre-fire stage, even before visible smoke appears. An additional advantage is the ability to minimise false alarms caused by ambient dust, a significant consideration in IT environments. Today, it is one of the leading technologies for protecting critical server rooms.

Détection de fumée par aspiration (HSSD  VESDA).png
Pictogramme utilisateur

Maxime, Technical Manager at Scutum Fire

“What really strikes our clients is the time gained. At a high-availability site equipped with a VESDA system, our sensors detected an abnormal increase in particles caused by an overheating connector more than four hours before any visible smoke appeared. The team was able to isolate the equipment and schedule maintenance, without triggering the extinguishing system or interrupting production.”

Other detection systems

Other technologies usefully complement this system: optical smoke detectors, heat detectors and linear heat detection systems, the latter being particularly suitable for monitoring cable trays. These systems do not offer the same level of detection sensitivity as HSSD, but they provide valuable additional protection in peripheral or less critical areas of the site: plant rooms, storage areas and circulation spaces.

The crucial intervention: automatic fire suppression solutions

One principle is clear from the outset: traditional water sprinklers should be avoided above server racks. Water is conductive, it can irreversibly damage electronic equipment, and the damage caused by an accidental discharge can exceed that caused by the fire itself. Data centre protection therefore relies on suppression technologies specifically designed to operate alongside electronic equipment.

Inert gas fire suppression (IG-55, IG-541, etc.)

The principle behind inert gases is to reduce the ambient oxygen concentration to a level at which combustion can no longer continue, while remaining compatible with short-term human occupancy. This approach has the advantage of being clean, leaving no residue to remove after discharge, and being safe for electronic equipment. However, it requires a room to be perfectly sealed in order to maintain the effective gas concentration, as well as a rigorous evacuation procedure for personnel.

Extinction par gaz inerte.png

Inhibitory gas fire suppression (Novec 1230, FM-200)

Inhibitory gases work differently: they chemically interrupt the combustion reaction without affecting the oxygen concentration. Their main advantage is the small storage volume required compared with inert gases, combined with very rapid dispersion and equally safe operation for electronic equipment. Novec 1230 is particularly distinguished by a more favourable environmental profile than previous generations of inhibitory gases, a criterion that is increasingly considered by sustainability and ESG departments.

High-pressure water mist fire suppression

Counter-intuitive at first in an environment where water is considered a threat, high-pressure water mist operates according to a different principle from conventional sprinklers: micro-droplets projected at very high pressure absorb heat and suppress the fire while using a minimal amount of water. The result is a non-toxic, environmentally friendly system that actively cools the affected area. It is a particularly relevant option for large volumes or areas with specific risks, such as battery rooms.

Extinction par brouillard d'eau haute pression.png
Pictogramme utilisateur

Xavier, Project Manager at Scutum Fire

“We equipped a Tier III data centre of approximately 800 m², including a lithium-ion battery room, with a high-pressure water mist system. The result: less than ten litres of water used per discharge in the tested area, compared with several hundred litres for a conventional sprinkler system, with cooling that was at least as effective.”

These three technologies meet different needs. The table below summarises the main considerations.

Technology Advantages Limitations Ideal for
Inert gas (IG-55, IG-541…) No residue, no impact on electronic equipment, proven and recognised fire suppression performance Requires a fully sealed room, evacuation procedures must be followed Medium to large server rooms, enclosed environments
Inert gas (Novec 1230, FM-200) Low storage space requirements, very rapid discharge, safe for electronic equipment Higher gas cost, refilling must be planned after activation Space-constrained areas where storage space for gas reserves is limited
High-pressure water mist Non-toxic, environmentally friendly, actively cools the area, very low water consumption Requires a suitable nozzle network and appropriate pressure, technically complex installation Large spaces, battery areas, sites combining IT rooms and technical areas

Beyond technology: prevention and good practice

The best detection and suppression technology is not sufficient on its own. Fire safety in a data centre relies on a holistic approach, in which technology is just one link in the chain.

1 Compartmentation and fire resistance

fire-resistant walls and doors, together with careful sealing of cable penetrations, to prevent a localised fire from spreading to the rest of the site.

2 Preventive maintenance

the best system is worthless without regular maintenance. Maintenance contracts and mandatory periodic testing ensure that equipment remains operational when it is needed.

3 Emergency response plan and staff training

knowing how to react during the first few minutes can often make the difference between a controlled incident and a disaster.

Calfeutrement coupe-feu.png
Porte coupe feu.png

These three points form a genuine checklist that should not be overlooked: they determine the actual effectiveness of the entire fire safety system, well beyond the performance of the equipment installed.

Conclusion: make fire safety a pillar of your digital resilience

Fire safety in a data centre is never about a single system. It is a chain: prevention, early detection, appropriate suppression and rigorous maintenance. Every link matters, and it is the strength of the whole chain that truly protects your data and your business.

Given the scale of the potential consequences of a fire, this type of protection should be considered an investment, rather than simply another expense.

Is your data centre protected in proportion to its value? Our experts are available to carry out a complete audit and recommend the solution best suited to your requirements. Contact SCUTUM today.

Opératrice et opérateur dans un centre de télésurveillance APSAD P5

FAQ: frequently asked questions about fire safety in data centres

What is the best fire suppression solution for a data centre?

There is no single answer: the choice depends on the size of the room, the budget and the criticality of the equipment being protected. Inert gas and Novec 1230 remain standard solutions for protecting server racks, while water mist is particularly relevant for large volumes or areas with specific risks, such as batteries. The right solution is always the one that results from a tailored risk assessment.

Is water completely prohibited in a data centre?

Traditional sprinklers should be avoided above servers because of the damage they can cause. High-pressure water mist is, however, an exception: it uses around 90% less water than a conventional sprinkler, such a small quantity that it evaporates quickly, causing little or no damage.

Is BS 5839-1 mandatory?

BS 5839-1 is a British Standard, not legislation in itself. Its application should be considered alongside the legal requirements that apply to the premises, including the Regulatory Reform (Fire Safety) Order 2005 in England and Wales. It is nevertheless a key technical reference for the design, installation, commissioning and maintenance of fire detection and alarm systems.

How long does it take to install a fire protection system?

This varies considerably: from a few days for a small room to several weeks for a large data centre. The determining factors are the technology selected (pipework for a gas suppression system), the need to carry out work outside production hours and the overall complexity of the site.

Is a gas suppression system dangerous for staff?

These systems are designed to remain safe: an alarm followed by a time delay allows evacuation before discharge. Inert gases reduce the oxygen concentration, but to a level that remains breathable for a short period. Inhibitory gases are also safe at the concentrations used.

Why is early detection (HSSD/VESDA) so important?

It identifies the early signs of a fire and particles associated with overheating long before visible smoke or flames appear. This provides valuable time for human intervention, such as disconnecting a faulty power supply, before automatic suppression becomes necessary. This is often what prevents a service interruption.

What is the lifespan of a fire protection system?

Equipment, including detectors and nozzles, has an average lifespan of 10 to 15 years. Gas cylinders and containers, meanwhile, must undergo periodic inspection and testing, generally every 10 years. Rigorous maintenance remains the key to the longevity and reliability of the entire system.

What budget should be allowed for fire protection in a data centre?

The cost can range from a few thousand pounds for a small room to several hundred thousand pounds for a large site. It should always be considered in relation to the value of the protected assets, both equipment and data, as well as the actual cost of business downtime. Viewed from this perspective, it is an investment in business resilience rather than simply an expense.